Commercial kitchen ventilation equipment is built for grease-laden cooking environments and governed by NFPA 96, which sets requirements for grease duct construction, clearances, and cleaning access. Type I hoods are required over grease-producing equipment and must pair with grease-rated ductwork; Type II hoods handle heat- or steam-only equipment and don't require grease-rated construction.
Simplified schematic — actual configurations vary by manufacturer and application.
Typical Specifications
- Grease duct slope: minimum ~2% (1/4 in. per foot) toward the hood or grease reservoir
- Cleanout access at every change of direction and at intervals not exceeding 12 ft
Common Use Cases
- Restaurant and food-service hood exhaust
- Grease duct exhaust fans built to run continuously at elevated exhaust temperatures
- Kitchen make-up air balancing
Configurations
- Upblast exhaust fans with a hinged, tilt-up base for duct and fan-cavity cleaning access
- Integrated grease cup or drainage on the fan housing
- Type I (grease) and Type II (heat/steam) hood assemblies
Certifications & Standards
Equipment in this category is commonly available with:
- UL 705 Supplement SC listing (formerly UL 762) for grease-laden exhaust
- Built to NFPA 96 requirements